Precautions when installing explosion-proof electromagnetic flow meter
Author: PhilemonTime: 2020-01-06
Precautions when installing explosion-proof electromagnetic flow meter
1. The axis of the non-measuring electrode must be approximately horizontal;
2. The measuring pipe must be completely filled with liquid;
3. There must be at least 5 * D (D is the inside diameter of the flowmeter) straight pipe section in front of the flowmeter, and at least 3 * D (D is the inside diameter of the flowmeter) length straight pipe section at the rear;
4. The direction of fluid flow is the same as the arrow direction of the flow meter;
5. A vacuum in the pipeline will damage the lining of the flowmeter, so special attention should be paid;
6. There should be no strong electromagnetic field near the flowmeter;
7. There should be ample space near the flow meter for installation and maintenance.